![]() |
| 4-265 Nils Hasselmo Hall - Walk In cooler |
Room 4-265 Nils Hasselmo Hall - Walk in Cooler.
Reported by/time reported: Brent Garberg W002074867 - 11am
FM on site 11am
Time emergency personnel on site:11:30 am DEHS
UMPD contacted 11:33am
DEM contacted 11:36 - Lisa Dressler
DEM page out 11:46am with status update.
Brief description of
event:
Over the weekend, a cold room went into alarm. This was in an empty lab area. The mechanic checked it and since it was empty,
it was decided to leave it until Monday.
The walk in kept getting colder, and the water pipe for the faucet in
that room was frozen. On Monday, the
pipefitter was able to replace a sensor, and the cold room warmed up and the
pipe blew. He was able to get the water
shut off fairly quickly. There were
approximately 100 gallons of water, and it was cleaned up with FM staff. Neil Carlson and Cheryl Miller were called to
assess.
![]() |
| The base of the faucet was the source of the leak. |
![]() |
| No shut off valve below the sink. |
Chain of escalation:
Brent notified Karen Collins and Nick Manthey , and several trades
and custodians were running wet vacs.
Water was cleaned up by 11:40. Neil Carlson, Cheryl Miller, Sam Talbert and
FM staff were called. No customers were
affected.
Causal
Factors:
The walk in cooler started to drop in temperature, a water
faucet in the room froze, and when the
unit started running normally, a pipe burst.
Action taken to
remediate:
Water was cleaned up very quickly. Base was removed from cabinets and holes were drilled. Fans were put up. Neil will be coming back on Tuesday to check for moisture. The cooler will need mold remediation by FM Abatement because of mold growth on boxes and on the light fixtures.
Water was cleaned up very quickly. Base was removed from cabinets and holes were drilled. Fans were put up. Neil will be coming back on Tuesday to check for moisture. The cooler will need mold remediation by FM Abatement because of mold growth on boxes and on the light fixtures.
| Mold on light fixture |
What could have been
done to avoid the situation?
The walk in cold room should have been monitored throughout
the weekend. Since it was empty, it
could have been turned off or the door could have been propped open. The pipefitter could have been called in as
well.
Actions to be taken
to avoid situation from occurring in the future: Notification of this issue was sent to the
supervisor on duty and the mechanic and supervisor that first went to look at
the cold room. It is on the agenda for
a district discussion.
Follow-up inspection 10/22/2013
There is a bubble on the seamless floor in the walk in cooler that needs to be repaired.
The base of the walls and interior insulation in 4-263 will need to be removed as the wall is not drying out .
Follow-up inspection 10/22/2013
There is a bubble on the seamless floor in the walk in cooler that needs to be repaired.
| Bubble on floor next to cooler entrance |
![]() |
| Cold area of the wall inside 4-263 was confirmed wet with a moisture meter. |
Electrical check
| Circuit #2 and #12 were warm for N4LE. Circuit #24 was warm for N4LG. These may be only the circuits used for the floor fans but they should be checked for possible defect. |
![]() |
| #24 N4LG |
#2 N4LE
![]() |
| #12 N4LE |








No comments:
Post a Comment